Honeywell 301c Uživatelský manuál Strana 96

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 228
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 95
94 301C User Manual M-510324
Honeywell 7/10
BACnet/IP MODULE
Honeywell Products and BACnet Objects
Object Names
Object names are constructed in two parts, as follows:
Part one: The device display label (product name) for the network in
which the object resides. This value is editable only when
using the 301C controller.
Part two: Unique tag label among all the objects for the same device.
Ex : “301D2 CO2 AD:14.CO2” where ‘301D2 CO2 AD:14’ is the
device display label and ‘CO2’ is the unique tag label that identifies the
object as a CO2 sensor.
Vulcain Object Tag Labels
Table 1:
Tag Labels Description
Object
Type
‘Gas label’ Gas sensor AI
.Alrm Simple alarm level AV
Amin /Amax Alarm level A and hysteresis AV
Bmin /Bmax Alarm level B and hysteresis AV
Cmin /Cmax Alarm level C and hysteresis AV
relx Relay output X (1 to 8) BO
buzz Buzzer output BO
.outx Output X (1 to 3) BO or BV
.AIx Analog input X (1 to 16) AI
.BIx Binary Input X (1 to 12) BI
.RH Relative Humidity sensor AI
.Temp Temperature sensor AI
Zobrazit stránku 95
1 2 ... 91 92 93 94 95 96 97 98 99 100 101 ... 227 228

Komentáře k této Příručce

Žádné komentáře