M-510324 301C User Manual 91
7/10 Honeywell
BACnet/IP MODULE
BACnet/IP MODULE
(BIP option)
Specifications
Ethernet Port : 10/100-compatible with 10 Base-T interface, RJ-45
Visual Indicators : Green LED LINK
Yellow LED ACT
Network Configuration: See 301C BACnet menu section.
BACnet/IP protocol
UDP Port: 47808. This value is not modifiable using the 301C.
The module has been developed as per ANSI/ASHRAE Standard 135-
2001 : BACnet®— A Data Communication Protocol for Building
Automation and Control Networks. The Data Link Layer option is per
BACnet/IP (Annex J).
http://www.ashrae.org/
BACnet Objects
BACnet objects represent any information available through the 301C
sub network. Each available value is represented by one object of a
specific type. There are currently 6 object types supported :
Analog Input represented by ‘AI’
Analog Value represented by ‘AV’
Binary Input represented by ‘BI’
Binary Output represented by ‘BO’
Binary Value represented by ‘BV’
Device represented by ‘DEV’