PRODUCT DATA
65- 0237- 1
CP-UM-5109E
® U.S. Registered Trademark
Copyright © 2000 Honeywell Inc. • All Rights Reserved
C6097A,B
Pressure Switches
APPLICATION
The C6097 Pressure Switches are safety devices used in
positive-pressure or differential-pressure systems to sense
gas or air pressure changes.
FEATURES
For use with natural gas, liquid propane (LP) gas,
or air.
Diaphragm-actuated safety-limit switch.
Switch can be wired to turn on alarm.
C6097A models break control circuit at setpoint
on pressure fall.
C6097B models break control circuit at setpoint
on pressure rise.
Lockout with manual reset and recycle options.
Lockout models have external manual reset
button.
Removable transparent cover protects scaleplate
and adjusting knob.
Pipe tappings allow selection of positive
pressure, differential pressure (air only) or
venting connections (NPT mount only).
1/4 in. NPT or flange mount models for direct
mounting to Honeywell Integrated Valve Train.
Optional switch position indicator lamp available.
IP54 enclosure standard.
Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc, 12 to 60 in.
wc or 1.5 to 7 psi.
Surge orifice.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 4
Wiring ............................................................................... 5
Settings and Adjustments ................................................. 5
Operation and Checkout .................................................. 6
Zobrazit stránku 0
1 2 3 4 5 6 7 8

Shrnutí obsahu

Strany 1 - Pressure Switches

PRODUCT DATA65- 0237- 1CP-UM-5109E® U.S. Registered TrademarkCopyright © 2000 Honeywell Inc. • All Rights Reserved C6097A,BPressure SwitchesAPPLICATI

Strany 2 - SPECIFICATIONS

C6097A,B PRESSURE SWITCHES65-0237—1 2ORDERING INFORMATIONWhen purchasing replacement and modernization products from your TRADELINE® wholesaler or dis

Strany 3 - C6097A,B PRESSURE SWITCHES

C6097A,B PRESSURE SWITCHES3 65-0237—1a Acceptable media: Natural gas, liquid propane (LP) gas, and air.Table 1. Pressure Switch Model Selection.Model

Strany 4 - INSTALLATION

C6097A,B PRESSURE SWITCHES65-0237—1 4Table 2. Switch Ratings (Amperes)Table 3. Alternate Electrical Ratings when used with Honeywell Flame Safeguard

Strany 5 - SETTINGS AND ADJUSTMENTS

C6097A,B PRESSURE SWITCHES5 65-0237—1WIRINGWARNINGElectrical Shock Hazard.Can cause serious personal injury or death.Disconnect power supply before be

Strany 6 - OPERATION AND CHECKOUT

C6097A,B PRESSURE SWITCHES65-0237—1 6OPERATION AND CHECKOUTOperationThe manual reset C6097A diaphragm actuates the snap-acting switch to break a contr