PCR-300PCR-300 RCInstallation and OperatingInstructionsElectronic refrigeration controlEB-PCR-04 EN1H-1924GE23 R1207
Three spot indicators show the switching status of the relays duringoperation:Pos. 1: On : Compressor relay on.Off: Compressor relay off.Flashes: Comp
11u Access the first programming level by pressing the and keys at the same time for 5 seconds.u Then use the and keys to access the parameters to
If the set temperature difference E03 is negative, an alarm is givenif it is too cold in the refrigerated area, e.g. E03 = –10 K, cold store setpoint
6.7 Manual defrostingPress and hold down the key for 5 seconds. The manual defrosting process will be initiated.7 ProgrammingAccess to the second pro
14The time is entered in increments of 10 minutes in each case .Important: The times must be entered in ascending order.E03 Alarm temperature differen
15E15 Sensor calibration T1 –5 to +5 K 0 K(cold store)E16 Sensor calibration T2 –5 to +5 K 0 K(evaporator)E17 Operation of 0 = Relay de-energizes 2co
168 MaintenanceThe controller does not require any maintenance. It does not have anyfuses so, if brief voltage spikes occur, the refrigeration system
Clearing alarm:Press the key.All alarm messages, with the exception of AL2, are also reset byswitching off the operating voltage. AL2 can only be res
1812 Technical dataMains voltage/frequency 230 V AC ± 10% / 50/60 HzRated wattage 2.5 wattsDisplay 3-digit, 7-segment, red LED, 14.2 mmResolution 1 KM
19EC Declaration of Conformityas defined in the EMC Directives 89/336/EECand theEC Low Voltage Directives 73/23/EECProduct: FLICA, electronic coldstor
2TABLE OF CONTENTS11 Unpacking the unit and conditions of use312 General instructions 313 Use and function 33.1 Use for the purpose intended 33.2 Func
Automation and Control SolutionsHoneywell GmbHHardhofweg • 74821 Mosbach / GermanyPhone: +49 (0) 62 61 / 81-475Fax: +49 (0) 62 61 / 81-461E-Mail: Cool
31 Unpacking the unit and conditions of useBefore and when unpacking the unit, make a visual inspection toidentify any possible damage which may have
I The controller must not be used as a safety cut-out device or excesstemperature limiter.If the controller is used for purposes other than those stat
I Never expose the unit to excessive heat, dust and vibrations. Avoidknocks and pressure loads. If the housing is damaged, there is a riskof an electr
6a) housing with 2 mounting tabs:open out the lateral mounting tabs; clip the unit on the 35 mm railand press tabs in again.b) housings with 1 mountin
7Terminal: Description:1 - 2 T1 = Cold store sensor3 - 4 T2 = Evaporator sensor 10 - 12 Mains = Power supply13 - 15 V = Compressor contactor (cool
85.3 Setting the DIP switch for the emergency setpoint and theclock back-up batteryCarefully lift the housing cover off the side, using your fingers.I
☛ Note: It takes approximately 24 hours for the battery to achieve itsfull back-up capacity.The battery will provide cover for a power failure of appr