HoneywellPROTECTORELAY OIL BURNER CONTROLSTHESEONE-PIECE.STACK-MOUNTEDOIL BURNER PRIMARY CONTROLS CYCLE THE BURNER ON THERMOSTAT DEMAND AND S
Burner Does Not Start When Thermostat Calls For Heat PRELIMINARY CHECKS1. Ensure all limit switches are closed.2. Ensure safety switch is reset.3. Che
IMPORTANTTHE SPECIFICATIONS GIVEN IN THIS PUBLICATION DO NOT INCLUDE NORMAL MANUFACTURING TOLERANCES. THEREFORE, UNITS MAY NOT MATCH T
AMBIENT TEMPERATURE:Operating: 0° F to 104” F [-18“ C to 40° C]. Shipping: -40° F to 150° F [-40° C to 66° C], DIMENSIONS: Referto Fig. 1.ELECTRICAL R
WHEN INSTALLING THIS PRODUCT...1. Read these instructions carefully. Failure to follow them could damage the product or cause hazardous
A DO NOT FORCE THE COLLAR OF THE MOUNTING FLANGE PAST THE STOP.FIG. 2—MOUNTING AND LOCATION CONSIDERATIONS.• Locate the control between the boiler or
FIG. 4—RA116A WIRING DIAGRAM WITH A LINE VOLTAGE THERMOSTATOR CONTROLLER.RA117ASERIES 10 THERMOSTAT ^OIL VALVE IBURNERMOTORIGNITIONLI^{HOT)HIGHLIMIT&
A POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.A USE GREEN TERMINAL TO CONNECT CASE TO GROUND.A CONTACTS BREAK IN SEQUEN
STARTUP AND CHECKOUTWARNINGFIRE HAZARDCAN CAUSE SEVERE BURNSEnsure the combustion chamber is free of oil or oil vapor before starting system.STEP THE
TROUBLESHOOTING AND MAINTENANCETo cxsmpletely troubleshoot an oil burner installation, check the burner, ignition transformer, and oil pr