Honeywell NXL Uživatelský manuál

Procházejte online nebo si stáhněte Uživatelský manuál pro Numerické klávesnice Honeywell NXL. Honeywell NXL User's Manual Uživatelská příručka

  • Stažení
  • Přidat do mých příruček
  • Tisk

Shrnutí obsahu

Strany 1 - USER’S MANUAL

NXL HVAC & COMPACT USER’S MANUAL

Strany 2

10(96) EU Directive HoneywellHoneywellHoneywellHoneywell 2 All NX frequency converters fulfil all EMC immunity requirements (standards EN 61000-6

Strany 3

EU Directive 11(96) 2 EU DECLARATION OF CONFORMITY We Manufacturer's name: Vacon Oyj

Strany 4

12(96) EU Directive HoneywellHoneywellHoneywellHoneywell 2 EU DECLARATION OF CONFORMITY We Manufacturer's name: Vacon Oyj Manufacturer&apo

Strany 5

Receipt of delivery 13(96) 3 3. RECEIPT OF DELIVERY NXL frequency converters have undergone scrupulo

Strany 6

14(96) Receipt of delivery HoneywellHoneywellHoneywellHoneywell 3 3.2 Type designation code NXL HVAC HVAC03C2Enclosure & EMC classification2

Strany 7 - 1. SAFETY

Receipt of delivery 15(96) 3 3.5 Warranty Only manufacturing defects are covered by the warranty. The m

Strany 8 - HOT SURFACE

16(96) Technical data HoneywellHoneywellHoneywellHoneywell 4 4. TECHNICAL DATA 4.1 Introduction Honeywell NXL is a compact frequency converter wi

Strany 9 - 2. EU DIRECTIVE

Technical data 17(96) 4 Figure 4-1. NXL block diagram

Strany 10

18(96) Technical data HoneywellHoneywellHoneywellHoneywell 4 4.2 Power ratings 4.2.1 NXL Compact – Mains voltage 208 – 240 V & 380 – 500 V

Strany 11 - EU DECLARATION OF CONFORMITY

Technical data 19(96) 4 4.2.1 NXL HVAC – Mains voltage 380 – 500 V Mains voltage 380-500 V, 50/60 Hz,

Strany 12

AT LEAST THE 11 FOLLOWING STEPS OF THE START-UP QUICK GUIDE MUST BE PERFORMED DURING THE INSTALLATION AND COMMISSIONING. IF ANY PROBLEMS OCCUR, PLEAS

Strany 13 - 3. RECEIPT OF DELIVERY

20(96) Technical data HoneywellHoneywellHoneywellHoneywell 4 4.3 Technical data Input voltage Uin 380 - 500V, -15%...+10% 3~ 208…240V, -15%...+10

Strany 14

Technical data 21(96) 4 Immunity Complies with EN50082-1, -2, EN61800-3 EMC Emissions MF2-MF3: EMC l

Strany 15

22(96) Installation HoneywellHoneywellHoneywellHoneywell 5 5. INSTALLATION 5.1 Mounting 5.1.1 NXL Compact (MF2 and MF3) There are two possible p

Strany 16 - 4. TECHNICAL DATA

Installation 23(96) 5 Figure 5-3. NXL Compact dimensions, MF2 Table 5-1. Dimensions of NXL, MF2

Strany 17

24(96) Installation HoneywellHoneywellHoneywellHoneywell 5 Figure 5-4. NXL Compact dimensions, MF3 W1 W2 W3 H1 H2 H3 H4 H5 H6 H7 D1 D

Strany 18 - EMC-level N

Installation 25(96) 5 5.1.2 NXL HVAC (MF4 – MF6) The frequency converter shall be fixed with fou

Strany 19

26(96) Installation HoneywellHoneywellHoneywellHoneywell 5 CANK5_2DBAB 5.2 Cooling Forced air flow cooling is used for NXL HVAC and NXL Compact s

Strany 20

Installation 27(96) 5 5.3 Changing EMC protection class from H/C to T in NXL HVAC The EMC protect

Strany 21

28(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6. CABLING AND CONNECTIONS 6.1 Power connections Figure 6-1. Power connect

Strany 22 - 5. INSTALLATION

HoneywellHoneywellHoneywell Cabling and connections 29(96) 6 6.1.1 Cabling Use cables with heat resistance of at least +70°C. The cables and th

Strany 23

CONTENTS NXL HVAC & COMPACT USER’S MANUAL INDEX 1 SAFETY 2 EU DIRECTIVE 3 RECEIPT OF DELIVERY 4 TECHNICAL DATA 5 INSTALLATION 6 CABLIN

Strany 24 - Honeywell

30(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.1.1.1 Cable and fuse sizes Terminal cable size (min/max) Frame Type I

Strany 25

Cabling and connections 31(96) 6 6.1.2 Mounting of cable accessories Enclosed to your NXL frequency converter you have received a plastic bag c

Strany 26

32(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 5. Place the rubber grommets in the openings as shown in Figure 5. 6. Fix

Strany 27

Cabling and connections 33(96) 6 6.1.3 Installation instructions 1 Before starting the installation, check that none of the components of the

Strany 28 - L1 L2 L3

34(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.1.3.1 Stripping lengths of motor and mains cables Figure 6-5.Stripping of

Strany 29

Cabling and connections 35(96) 6 6.1.3.2 Installation of cables to NXL Note: In case you want to connect an external brake resistor (MF3 and b

Strany 30

36(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 Figure 6-8. NXL Compact, MF3 Figure 6-9. Cable installation in NXL Compact

Strany 31

Cabling and connections 37(96) 6 Installation of an external RFI filter to NXL Compact (MF2-3) The EMC protection class of NXL Compact frequenc

Strany 32

38(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 RFI Filter type Input voltage Dimensions WxHxD (mm) NXLRFIV35 380-500V 3~

Strany 33

Cabling and connections 39(96) 6 Figure 6-13. NXL HVAC (03-12), MF4 Figure 6-14. Cable installation in NXL HVAC (03-12), MF4 Earth terminals

Strany 34 - MAINS MOTOR

ABOUT THE NXL HVAC & COMPACT USER'S MANUAL AND NXL APPLICATION MANUALS Congratulations for choosing the Smooth Control provided by NXL freq

Strany 35

40(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 Figure 6-15. NXL HVAC (16-31), MF5 Figure 6-16. Cable installation in NXL

Strany 36

Cabling and connections 41(96) 6 Figure 6-17. NXL HVAC (38-61), MF6 Figure 6-18. Cable installation in NXL HVAC (38-61), MF6 Brake resistor

Strany 37

42(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.1.4 Cable installation and the UL standards To meet the UL (Underwriters

Strany 38 - WxHxD (mm)

Cabling and connections 43(96) 6 6.2 Control unit 6.2.1 NXL Compact (MF2 – MF3) The control unit of the NXL frequency converter is integrated

Strany 39 - DC terminals

44(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.2.3 Control connections The basic control connections are shown below. T

Strany 40

Cabling and connections 45(96) 6 6.2.4 Control I/O Terminal Signal Description 1 +10Vref Reference output Voltage for potentiometer, et

Strany 41

46(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.2.5 Control terminal signals Terminal Signal Technical information 1 +1

Strany 42 - MF6 4 35

Cabling and connections 47(96) 6 6.2.5.1 Jumper selections on NXL basic board The user is able to customise the functions of the frequency con

Strany 43 - Slot D: Fieldbus boards

48(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 Figure 6-23. Jumper selection for NXL HVAC, MF4 – MF6 !!!!WARNING Check th

Strany 44 - 21 22 23

Cabling and connections 49(96) 6 Figure 6-24. The location of jumper blocks in MF2 (left) and MF3 (right) Figure 6-25. The location of jumper

Strany 45 - Can be programmed as DIN4

HoneywellHoneywellHoneywellHoneywell Index 5(96) NXL HVAC & COMPACT User's Manual Index Date: 28.

Strany 46

50(96) Cabling and connections HoneywellHoneywellHoneywellHoneywell 6 6.2.6 Motor thermistor (PTC) connection There are three possibilities to con

Strany 47

Control Keypad 51(96) 7 7. CONTROL KEYPAD The control keypad is the link between the NXL frequency converter and the user. The NXL control keypad f

Strany 48

52(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.1.2 Control place indications The symbols I/O term, Keypad and Bus/Comm (see chap

Strany 49 - Jumper block X7

Control Keypad 53(96) 7 7.2 Keypad push-buttons The NXL seven-segment control keypad features 7 push-buttons that are used for the control of the f

Strany 50 - GND (terminal 11)

54(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 = Start button. Pressing this button starts the motor if the keypad is the act

Strany 51 - 7. CONTROL KEYPAD

Control Keypad 55(96) 7 7.4 Navigation on the control keypad The data on the control keypad are arranged in menus and submenus. The menus are used

Strany 52

56(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 Figure 7-4. Keypad navigation chart STOPREADYI/O termenterenterresetenterSTOPI/O

Strany 53

Control Keypad 57(96) 7 Menu functions Code Menu Min Max Selections M1 Monitoring menu V1.1 V1.24 See chapter 7.4.1 for the monitoring values

Strany 54 - START-UP WIZARD

58(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.1 Monitoring menu (M1) You can enter the Monitoring menu from the Main menu by

Strany 55 - Location

Control Keypad 59(96) 7 Code Signal name Unit ID Description V1.1 Output frequency Hz 1 Frequency to the motor V1.2 Frequency reference H

Strany 56 - No editing!

6(96) Index 6.2.5 Control terminal signals... 46 6.

Strany 57 - Menu functions

60(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.2 Parameter menu (P2) Parameters are the way of conveying the commands of the u

Strany 58 - Figure 7-5. Monitoring menu

Control Keypad 61(96) 7 Figure 7-6. Parameter value change procedure enterSTOPI/O termREADYSTOPI/O termREADYSTOPI/O termREADYSTOPI/O termREADYS

Strany 59

62(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.3 Keypad control menu (K3) In the Keypad Controls Menu, you can choose the cont

Strany 60

Control Keypad 63(96) 7 7.4.3.2 Keypad reference The keypad reference submenu (R3.2) displays and allows the operator to edit the frequency refere

Strany 61 - Control Keypad 61(96)

64(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.4 Active faults menu (F4) The Active faults menu can be entered from the Main m

Strany 62 - Fieldbus

Control Keypad 65(96) 7 7.4.5 Fault codes The fault codes, their causes and correcting actions are presented in the table below. The shadowed fault

Strany 63

66(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 17 Motor underload/ Pump Dry detection/ Broken belt Detection Motor underload protec

Strany 64 - Table 7-3. Fault types

Control Keypad 67(96) 7 53 Fieldbus fault The data connection between the fieldbus Master and the fieldbus board is broken Check installation. If

Strany 65

68(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.7 System menu (S6) The System menu can be entered from the main menu by pushing

Strany 66

Control Keypad 69(96) 7 T6.8.2.4 Operating hours trip counter hh:mm: ss P6.8.2.5 Clear operating time counter 0 = No action 1 = Clea

Strany 67 - Push Enter to reset!

HoneywellHoneywellHoneywell Safety 7(96) 1 1. SAFETY 1.1 Warnings 1 The components of the p

Strany 68

70(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.7.1 Copy parameters The Copy parameters submenu (S6.3) is located under the Sys

Strany 69 - Control Keypad 69(96)

Control Keypad 71(96) 7 Figure 7-11. Parameter locking 7.4.7.3 Keypad settings In the submenu S6.6 under the System menu you can further customise

Strany 70 - Parameter lock (P6.5.2)

72(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 Timeout time (P6.6.3) The Timeout time setting defines the time, after which the key

Strany 71 - Default page (P6.6.1)

Control Keypad 73(96) 7 HMI acknowledge timeout (P6.7.3) This function allows the user to change the timeout of the HMI acknowledgement time. Note!

Strany 72 - Fan control (P6.7.2)

74(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 Counters submenu (S6.8.1) In the Counters submenu (S6.8.1) you can find information r

Strany 73

Control Keypad 75(96) 7 Software info submenu (S6.8.3) The following information can be found under the Software info submenu (S6.8.3): Page Conte

Strany 74

76(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 For more information on the expander board-related parameters, see Chapter 7.4.9. Fig

Strany 75

Control Keypad 77(96) 7 7.4.8 Modbus interface NXL has a built-in Modbus RTU bus interface. The signal level of the interface is in accordance wit

Strany 76

78(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.8.2 Termination Resistor The RS-485 bus is terminated with 120 Ω termination

Strany 77

Control Keypad 79(96) 7 Status Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 - - - - - - - - F Z AREF W FLT DIR RUN RDY

Strany 78

8(96) Safety HoneywellHoneywellHoneywellHoneywell 1 1.3 Earthing and earth fault protection The Honeywell NXL frequency converter must always be

Strany 79

80(96) Control Keypad HoneywellHoneywellHoneywellHoneywell 7 7.4.8.5 Fieldbus parameters RS-485 communication status (I6.10.1) With this functio

Strany 80

Control Keypad 81(96) 7 Communication time-out (P6.10.7) If communication between two messages is broken for a longer time than that defined by this

Strany 81

82(96) Commissioning HoneywellHoneywellHoneywellHoneywell 8 8. COMMISSIONING 8.1 Safety Before commissioning, note the following directions and war

Strany 82

Commission

Strany 83

84(96) Commissioning HoneywellHoneywellHoneywellHoneywell 8 9 Run the start-up tests without the motor being connected to the process, if possible.

Strany 84

Commission

Strany 85 - Table 8-1. Monitoring values

86(96) Commissioning HoneywellHoneywellHoneywellHoneywell 8 8.3.2 HVAC parameters in NXL HVAC (Control keypad: Menu P2  B2.1) Code Parameter

Strany 86

Commission

Strany 87

88(96) Commissioning HoneywellHoneywellHoneywellHoneywell 8 P2.1.16 P2.1.15.16 Analogue output function 0 12 1 307 0=Not used 1=Output freq. (0

Strany 88 - 9. FAULT TRACING

Fault tracing 89(96) 9 fault can be reset with the Reset button on the control keypad or via the I/O terminal. The faults are stored in the Fault hi

Strany 89

EU Directive 9(96) 2 2. EU DIRECTIVE 2.1 CE marking The CE marking on the product guarantees

Strany 90

90(96) Fault tracing HoneywellHoneywellHoneywellHoneywell 9 17 Motor underload/ Pump Dry detection/ Broken belt Detection Motor underload protect

Strany 91 - Fault tracing 91(96)

Fault tracing 91(96) 9 53 Fieldbus fault The data connection between the fieldbus Master and the fieldbus board is broken Check installation. If i

Strany 92

92(96) HoneywellHoneywellHoneywellHoneywell 10 10. DESCRIPTION OF EXPANDER BOARD NXLOPTAA Description: I/O expander board with one relay

Strany 93

Expander board NXLOPTAI 93(96) 11 11. DESCRIPTION OF EXPANDER BOARD NXLOPTAI Description: I/O expander board with one relay output (NO), thre

Strany 94

94(96) Expander board NXLOPTAI HoneHoneHoneHoneywellywellywellywell 11 Terminal Parameter setting Description X4 12 +24V Control voltag

Strany 95

NXL HVAC Basic speed control – Quick setup 95(96) 12 12. NXL HVAC BASIC SPEED CONTROL – QUICK SETUP This chapter provides basic setup instructions

Strany 96

Automation and Control Solutions Honeywell GmbH Böblinger Str. 17 71101 Schönaich, Germany Telephone (49) 7031 637 01 Telefax (49) 7073 637

Komentáře k této Příručce

Žádné komentáře